FIREYE
®
E300
EXPANSION MODULE
For use with the Fireye
FLAME-MONITOR
™
Control
DESCRIPTION
The FIREYE
E300 Expansion Module provides increased interlock supervision capability of the
FLAME-MONITOR System. The Expansion Module connects to any EB700 FLAME-MONITOR
Chassis by means of a ribbon cable. (P/N E350-3, E350-6).
By wiring any of sixteen interlock switches into the Expansion Module, the FLAME-MONITOR
display automatically acts as a “first-out” annunciator for these interlocks. In addition, a fuel selection
circuit is standard. The E300 is shipped with default messages associated with each set of terminals.
The user has the ability to modify these lockout messages in one of two ways:
1. Use the ED510 display module to select a lockout alarm message for the individual terminals of
the E300 from a library of available messages. Refer to Bulletins E-1101 or ED-5101 (E300
MESSAGE SELECT section).
2. Program a customized message (up to 40 characters in length) for the individual terminals of the
E300 using an IBM compatible PC with the E300 programming software (available at no charge
from Fireye) and the appropriate hardware. On most PC’s Windows Hyperterminal can be used to
program E300 messages.
Note: Modifying the E300 messages requires an EP Programmer with an Engineering code of 28 or
later (Engineering codes are found after the date code, e.g. 9416-28).
The Expansion Module does not interfere with the normal operation of the FLAME-MONITOR
System. It expands the message and diagnostic capability.
The E300 expansion module provides operational information and reduces troubleshooting time and
expense. It expands the standard display messages of the FLAME-MONTOR to identify the specific
limit in the operating control circuit or running interlock circuit which caused the burner shutdown or
lockout. For a detailed description of the FLAME-MONITOR System, see Bulletin E-1101.
APPROVALS
Underwriters Laboratories Inc.: Listing, File #MH10808
Canadian Standards Association: LR7989/17617 Certification Record
Factory Mutual (FM): Approved
SPECIFICATIONS
Supply Voltage:120V (+ 10% - 15%), 50 / 60 Hz
Ambient Temperature Levels: -40 F to +125 F (-40 C to +50 C)
Response Time:170 milliseconds Purge/32 milliseconds Run
Weight: 0.5 lb.
Humidity: 85% R.H. non-condensing
E300 CONTROL
E350 RIBBON CABLE
E-3001
APRIL 8, 2013
U
L
APPROVED
LISTED
C