C6.1.6/0513-0515/E 33
Appendix 3: Parameter list level 1 (Pr1)
Parameter
Description
Unit
Factory
setting
Comment
C01
Compressor cut-in pressure setpoint
[bar]
4.0
Not used for Digital CFDE
C02
Compressor cut-out pressure setpoint
[bar]
2.0
Not used for Digital CFDE
C07
Refrigerant selection for regulation
[-]
R404A
R22, R407A, R407F, R507,
N40,DR33, R134a, R407C
C16
Digital compressor setpoint
[bar]
3.3
Not used for CFME & CFLE
C17
Proportional band for compressor regulation
[bar]
2.0
Not used for CFME & CFLE
C21
Cycle time for digital compressor
[Sec]
10
Not used for CFME & CFLE
C24
Minimum capacity for digital compressor
[%]
20
Not used for CFME & CFLE
C25
Maximum capacity for digital compressor
[%]
100
Not used for CFME & CFLE
E39
Condenser setpoint
[°C]
35.0
E46
Regulation band of variable fan
[°C]
10.0
N01
Current minute
[-]
[-]
N02
Current hour
[-]
[-]
N03
Date of month
[-]
[-]
N04
Month
[-]
[-]
N05
Year
[-]
[-]
T18
Access to Pr2 level
[-]
[-]
Password: 3 2 1
Table 24: Parameters level 1