Instruction Manual
D200129X012
2506/2516 Receiver/Controller
June 2017
11
Figure 11. Typical Transmitter and Receiver Installation with an Indicator and Remote Set Point Connection
DF5379‐A
A3702‐2
CONTROLLER/
TRANSMITTER
SUPPLY
3
2500
CONTROLLER/
TRANSMITTER
INDICATOR
SUPPLY
PANEL
LOADER
REMOTE
SET POINT
ADJUSTMENT
CENTRALIZED
CONTROL PANEL
CONTROLLER OUTPUT PIPING
2506/2516 REMOTE
RECEIVER/CONTROLLER
DIAPHRAGM ACTUATOR
CONTROL VALVE
RECEIVER/
CONTROLLER SUPPLY
4
1
2
NOTES:
1 PIPING FROM TRANSMITTER OUTPUT TO PANEL INDICATOR
2 PIPING FROM TRANSMITTER OUTPUT TO PANEL RECEIVER/CONTROLLER INSTRUMENT INPUT. SEE FIGURE 3 FOR CONNECTION LOCATION
3 PIPING FROM PANEL LOADER TO RECEIVER/CONTROLLER REMOTE SET POINT CONNECTION. SEE FIGURE 3 FOR CONNECTION LOCATION.
4 SEE FIGURE 3 FOR CONNECTION LOCATION.
4
Connections
WARNING
The controller is capable of providing full supply pressure to connected equipment. To avoid personal injury or property
damage caused by parts bursting from system overpressure, make sure the supply pressure never exceeds the maximum
safe working pressure of any connected equipment.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
To complete the installation of a receiver/controller, make connections with tubing and fittings between the
receiver/controller and the actuator. The fittings, tubing, and mounting parts required depend on the type number
and optional equipment such as filter, regulator, and bypass valve.