Schematics
This section includes loop schematics required for wiring of intrinsically safe installations. If you have any questions,
contact your Emerson Process Management sales office
.
Figure 13. CSA Loop Schematic
28B5744‐B
NOTES:
1. BARRIERS MUST BE CSA CERTIFIED WITH ENTITY PARAMETERS
 AND ARE TO BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURERS I.S. INSTALLATION INSTRUCTIONS.
2. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH
 THE CANADIAN ELECTRICAL CODE, PART 1.
3. IF HAND-HELD COMMUNICATOR OR MULTIPLEXER IS USED,
 IT MUST BE CSA CERTIFIED AND INSTALLED PER THE
 MANUFACTURE'S CONTROL DRAWING.
4. FOR ENTITY INSTALLATION: Vmax > Voc, Imax > Isc
 Ci + Ccable < Ca, Li + Lcable < La
CSA ENTITY INSTALLATION DRAWING
HAZARDOUS LOCATION
CLASS I, GROUPS A,B,C,D
CLASS II, GROUPS E,F,G
CLASS III
NON-HAZARDOUS LOCATION
CSA CERTIFIED BARRIER
SEE NOTE 3
FISHER DLC3010
Vmax = 30 VDC
Imax = 226 mA
Ci - 5.5 nF
Li = 0.4 mH