3. Mount the DVC6200 on the actuator as follows:
D If required, a mounting adaptor is included in the mounting kit. Attach the adaptor to the digital valve controller,
then attach the digital valve controller assembly to the actuator. The roller on the digital valve controller
feedback arm will contact the actuator cam as it is being attached.
D If no mounting adaptor is required, attach the digital valve controller and mounting kit assembly to the actuator.
The roller on the digital valve controller feedback arm will contact the actuator cam as it is being attached.
4. For remote mount applications, proceed to page 17 for DVC6205 base unit mounting. Otherwise, proceed to
Step 2—Connect the Pneumatic Tubing on page 19.
Bracket Mounted
The DVC6200 digital valve controller can be mounted to any quarter‐turn rotary actuator, as well as those that comply
with the NAMUR guidelines. A mounting bracket and associated hardware are required. Refer to figure 12.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure
that the above measures stay in effect while you work on the equipment.
M6 MOUNTING BOLTS (4)
W9715
Figure 12. Mounting on Quarter‐Turn Actuators

Other manuals for Fisher FIELDVUE DVC6200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200 and is the answer not in the manual?

Fisher FIELDVUE DVC6200 Specifications

General IconGeneral
TypeDigital Valve Controller
Operating Temperature Range-40 to 85 °C (-40 to 185 °F)
Enclosure RatingNEMA 4X, IP66
Input Signal4-20 mA, HART
Communication ProtocolHART
Supply Pressure1.4 to 7 bar (20 to 100 psi)
DiagnosticsValve signature
ApprovalsATEX, IECEx, FM, CSA
Power SupplyLoop powered