Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2017
14
Quarter-Turn Rotary Actuators
Integral Mounted Fisher Actuators
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to
be sure that the above measures stay in effect while working on the equipment.
2. Verify that the appropriate cam is installed on the actuator as described in the instructions included with the
mounting kit.
Figure 10. Mounting on Rotary Actuators
ROTARY MOUNTING KIT
(DVC6200 NOT SHOWN)
W9708
Figure 11. Rotary Actuator Mounting Variations
E1229
NOTE THE DIFFERENCE IN THE SHAPE AND LENGTH OF THE ROLLER ARM
ROLLER ARM
2052 SIZE 2 AND 3
1051/1052 SIZE 40-70
SIZE 1061 SIZE 30-100
ROLLER ARM
ROLLER ARM
2052 SIZE 1
1051 SIZE 33
1052 SIZE 20-33

Other manuals for Fisher FIELDVUE DVC6200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200 and is the answer not in the manual?

Fisher FIELDVUE DVC6200 Specifications

General IconGeneral
TypeDigital Valve Controller
Operating Temperature Range-40 to 85 °C (-40 to 185 °F)
Enclosure RatingNEMA 4X, IP66
Input Signal4-20 mA, HART
Communication ProtocolHART
Supply Pressure1.4 to 7 bar (20 to 100 psi)
DiagnosticsValve signature
ApprovalsATEX, IECEx, FM, CSA
Power SupplyLoop powered