3200 ET & RM
25
3 - PROGRAM LEVEL #1
Level #1 exit.
The valve returns in normal operation.
1.10. Cycle #6
Ex.: not used [6--OFF]
Note: not viewed if cycle #5 is set on OFF.
1.9. Cycle #5
Ex.: not used [5--OFF]
1.8. Cycle #4: Brine refill
(2)
Ex.: for ET, not used for RM [4--12.0]
1.7. Cycle #3: Rapid rinse
(2)
Ex.: for ET, not used for RM [3--10.0]
1.6. Cycle #2: Brine draw/slow rinse for ET
(2)
Ex.: for ET, not used for RM [2--60.0]
1.4. Regeneration time
Ex.: 2:00 [- - 2:00 - ]
1.3. System capacity in m
3
°tH
(1)
Ex.: 1200 m
3
°tH [- - - 1200]
1.1. Water Hardness in °tH
(1)
Ex.: 30 °tH [- - - - - 30]
The valve is in service position. To enter in the first
level, push and hold the button for 5 seconds.
1.2. Water Hardness after mixing valve in °tH
(1)
Ex.: 6 °tH [P - - - - -6]
R
EGENERATION CYCLE TIME SETTING.
1.5. Cycle #1: Backwash for ET
(2)
, signal for RM
Ex.: for ET: [1--10.0]
for RM: 6 minutes compulsory [ 1 ---6.0]
P
P
P
P
P
P
P
P
P
P
P
P
Note:
1. Push the button once
per display.
2. Option settings may be
changed by pushing the
and set buttons.
3. Depending on current valve
programming, some
displays will not be viewed
or set.
(1)
The unit of measure depends on the display format chosen. All examples above are based on
the cubic meter format. (see point 2.12).
(2)
Only available with down flow regeneration valves and Twin valves (DF & UF).
For up flow regeneration valves, the cycles below apply to:
- Cycle #1: Brine draw & slow rinse - Cycle #3: Rapid rinse
- Cycle #2: Backwash - Cycle #4: Brine refill
E
N
G
L
I
S
H