PARAMETER 7 – CENTRAL HEATING PUMP OVERRUN TIMER
6. Use buttons ‘+’ and ‘-‘ to modify the value of the
parameter within the prescribed limits
00 = 0 x 5” = 0”
90 = 90 x 5” = 450” (7.5 min)
The default value is 36 = 180” = 3 min
7. Press and release button ‘S’ to confirm. The parameter
number (7) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER 8 – D.H.W PUMP OVERRUN TIMER
6. Use buttons ‘+’ and ‘-‘ to modify the value of the
parameter within the prescribed limits
00 = 0 x 5” = 0”
90 = 90 x 5” = 450” (7.5 min)
The default value is 18 = 90” = 1.5 min
7. Press and release button ‘S’ to confirm. The parameter
number (8) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER NO. 9 – MINIMUM GAS PRESSURE SETTING
Not applicable for FLOWMAX burner (only for atmospheric burner)
P
ARAMETER NO.10 – MINIMUM CENTRAL HEATING OUTPUT SETTING
Not applicable for FLOWMAX burner (only for atmospheric burner)
P
ARAMETER NO.11 – MAXIMUM GAS PRESSURE AND MAX. CENTRAL HEATING OUTPUT SETTING
Not applicable for FLOWMAX burner (only for atmospheric burner)
P
ARAMETER NO.12 – IGNITION SEQUENCE SETTING
Not applicable for FLOWMAX burner (only for atmospheric burner)