PARAMETER 13 – D.H.W PRIORITY
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = off
01 = on (default = 120”)
7. Press and release button ‘S’ to confirm. The parameter number
(13) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P
ARAMETER 14 – TYPE OF BURNER
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter:
00 = water heater with atmospheric burner;
01 = water heater with FLOWMAX - 90
02 = water heater with FLOWMAX - 120;
03 = water heater with FLOWMAX - 170;
7. Press and release button ‘S’ to confirm. The parameter number (14)
will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P
ARAMETER 15 – ZONED SYSTEM
6. If the system is fitted with zone valves, set the parameter at ‘01’. If
a remote control is installed, an extra interface board must be
installed to control the zone valves. Then set the parameter at ‘01’.
7. Press and release button ‘S’ to confirm. The parameter number
(15) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P
ARAMETER 16 – TELEPHONE CONTROL
6. If a telephone interface is installed, enable the board by setting
parameter 16 at ‘01’;
7. Press and release button ‘S’ to confirm. The parameter number
(16) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
N.B.: The connection of the telephone interface to contact TA of the
terminal board must be wired in parallel with the remote control using
two non-polarised conductors.