Logix 3800zb Digital Positioner FCD AIIOM001030_EN 02/23
flowserve.com 23
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
A
B
C
D
E
F
G
Figure 23: Selectable Gain Switch
8.5 Jog Calibration Switch
(CAL_AUTO◄►CAL_JOG)
This switch selects between Auto and Jog calibration modes.
Auto The Auto setting works for most valves if the fully
opened position of the valve has a mechanical stop. In Auto
mode during a stroke calibration (Quick-Cal), the positioner
will fully close the valve and register the 0% position, then fully
open the valve to register the 100% position.
Jog Use the Jog setting if the fully opened position of the
valve has no hard stop and is manually set. In Jog mode during
a stroke calibration (Quick-Cal), the positioner will fully close
the valve and register the 0% position, then wait for the user
to move the valve to the 100% open position using the Up and
Down buttons. Press the ACCEPT/QUICK-CAL button to
accept the 100% location.
See section 9, Operations Calibration and Control, for more
information.
8.6 Valve Stability Switch
(LO_FRIC◄►HI_FRIC)
Not applicable.
8.7 Signal at Closed Switch (HART)
(4mA◄►20mA)
Normally this will be set to 4 mA for an Air-To-Open actuator
configuration, and 20 mA for Air-To-Close.
4 mA Selecting 4 mA will make the valve close when the
signal is low (4 mA) and open when the signal is high (20 mA).
20 mA Selecting 20 mA will make the valve close when the
signal is high (20 mA) and open when the signal is low (4 mA).
NOTE: When using an Analog Output (AO) function, the
AO signal corresponds with the Signal At Closed selection. If
the valve closes with a 4 mA signal, the AO will show a 4 mA
signal at closed. If the valve closes with a 20 mA signal, the
AO will show a 20 mA signal at closed.
8.8 HART Switch (HART)
(HART_6◄►HART_7)
For HART 6 protocol, select HART6. For HART 7, select
HART7.
More
Responsive
More
Stable

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Flowserve Logix 3800zb and is the answer not in the manual?

Flowserve Logix 3800zb Specifications

General IconGeneral
BrandFlowserve
ModelLogix 3800zb
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals