SPECIFICATIONS
Model
FP-68KM4 FP-80KM4
Number Of Fan Blowers Single Single
H 624 (173) 768 (213)
M 564 (157) 624 (173)
Nominal
Airflow
L
m
3
/h
(l/s)
468 (130) 516 (143)
H 3.2 3.8
M 2.8 3.2
Nominal
Cooling
Capacity*
L
KW
2.4 2.7
H 2.3 2.4
M 2.0 2.1
Nominal
Sensible
Cooling
Capacity
L
KW
1.8 1.9
H 3.2 3.4
M 2.8 3.0
Nominal
Heating
Capacity**
L
KW
2.5 2.7
H 1.55 1.65
M 1.4 1.5
Nominal
Heating
Capacity***
L
KW
1.3 1.3
Noise Level at
1 m(L/M/H)
dB(A) 39/41/43 42/44/46
Power Supply 230V/1PHASE/50HZ
Fan Motor Power Watt 58 61.1
Fan Motor Running
Current
Amp. 0.253 0.264
Fan Motor Starting
Current
Amp. 0.759 0.792
Operation Control & Thermostat Remote Controller and wiring controller
Chiller Water Flow
Rate
1/h 610 700
Heat Water Flow Rate 1/h 300 315
Chilled Water Pressure
Drop
KPa 9.7 12.4
Hot Water Pressure
Drop
KPa 1.1 1.2
Chilled Water Content 1 0.9015 0.9015
Hot Water Content 0.366 0.366
Cond. Drain
Connection I.D.
mm
(inch)
19.05(3/4〃)
L mm 575 575
W mm 575 575
Casing
Dimensions
D mm 290 290
Panel Dimensions mm
680×680×30
Gross Weight kgs 32 32
Connection Method Socket(Threaded Female)
In
mm
(inch)
19.05(3/4〃)
Water
Connection
Out
mm
(inch)
19.05(3/4〃)
Cooling *:27°C db/19.5°C wb entering air temperature,7°C entering water and 12°C leaving water temperature.
Heating**:20°C db entering air temperature ,70°C entering water and 60°C leaving water.
Heating***:20°C db entering air temperature, 50°C entering water and 40°C leaving water.