EasyManua.ls Logo

Foundation FP-102KM4 - SPECIFICATIONS

Default Icon
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 4 of 49
Ceiling cassette
Fan
Coil Unit
, 4
-
Model: FP-
KM
SPECIFICATIONS
Model
FP-68KM4 FP-80KM4
Number Of Fan Blowers Single Single
H 624 (173) 768 (213)
M 564 (157) 624 (173)
Nominal
Airflow
L
m
3
/h
(l/s)
468 (130) 516 (143)
H 3.2 3.8
M 2.8 3.2
Nominal
Cooling
Capacity*
L
KW
2.4 2.7
H 2.3 2.4
M 2.0 2.1
Nominal
Sensible
Cooling
Capacity
L
KW
1.8 1.9
H 3.2 3.4
M 2.8 3.0
Nominal
Heating
Capacity**
L
KW
2.5 2.7
H 1.55 1.65
M 1.4 1.5
Nominal
Heating
Capacity***
L
KW
1.3 1.3
Noise Level at
1 m(L/M/H)
dB(A) 39/41/43 42/44/46
Power Supply 230V/1PHASE/50HZ
Fan Motor Power Watt 58 61.1
Fan Motor Running
Current
Amp. 0.253 0.264
Fan Motor Starting
Current
Amp. 0.759 0.792
Operation Control & Thermostat Remote Controller and wiring controller
Chiller Water Flow
Rate
1/h 610 700
Heat Water Flow Rate 1/h 300 315
Chilled Water Pressure
Drop
KPa 9.7 12.4
Hot Water Pressure
Drop
KPa 1.1 1.2
Chilled Water Content 1 0.9015 0.9015
Hot Water Content 0.366 0.366
Cond. Drain
Connection I.D.
mm
(inch)
19.05(3/4)
L mm 575 575
W mm 575 575
Casing
Dimensions
D mm 290 290
Panel Dimensions mm
680×680×30
Gross Weight kgs 32 32
Connection Method Socket(Threaded Female)
In
mm
(inch)
19.05(3/4)
Water
Connection
Out
mm
(inch)
19.05(3/4)
Cooling *:27°C db/19.5°C wb entering air temperature,7°C entering water and 12°C leaving water temperature.
Heating**:20°C db entering air temperature ,70°C entering water and 60°C leaving water.
Heating***:20°C db entering air temperature, 50°C entering water and 40°C leaving water.