14
be connected with the inverter directly.
Step 3: AC Wiring
• Check the grid voltage and compare with the permitted voltage range (refer to technical data).
• Disconnect the circuit-breaker from all the phases and secure against re-connection.
• Trim the wires:
-
Trim all the wires to 52.5mm and the PE wire to 55mm.
-
Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
• Separate the AC plug into three parts as below.
-
Hold middle part of the female insert, rotate the back shell to loosen it and detach it from
female inset.
-
Remove the cable nut (with rubber insert) from the back shell.
• Slide the cable nut and then the back shell onto the cable.
• Push the threaded sleeve into the socket, tighten up the cap on the terminal.
L: Brown/Red Wire
N: Blue/Black Wire
PE: Yellow & Green Wire
Note: Please refer to local cable type and color for actual
installation.