FPI P36D Zero Clearance Direct Vent Gas Fireplace
28
V
H1
H
V1
INSTALLATION
Vertical Venting with Two (2) 90
o
Elbows
With these options, max. total
pipe length is 30 feet with min.
of 7 feet total vertical and max.
8 feet total horizontal.
Please note min. 1 foot
between 90
o
elbows is re-
quired.
Vertical Venting with Three (3) 90
o
Elbows
Option V H + H1 V + V1
A) 0' Min. 2' Max. 2' Min.
B) 1' Min. 2' Max. 3' Min.
C) 2' Min. 3' Max. 4' Min.
D) 3' Min. 4' Max. 6' Min.
E) 4' Min. 5' Max. 7' Min.
F) 5' Min. 6' Max. 8' Min.
G) 6' Min. 7' Max. 9' Min.
H) 7' Min. 8' Max. 10' Min.
With these options, max.
total pipe length is 30 feet
with min. of 10 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.
One 90
o
elbow = Two 45
o
elbows.
One 90
o
elbow = Two 45
o
elbows.
V1
V
H
Lengths do not include elbow indicated.
Lengths do not include elbow indicated.
Option V H V + V1
A) 0' Min. 2' Max. 1' Min.
B) 1' Min. 4' Max. 3' Min.
C) 2' Min. 5' Max. 4' Min.
D) 3' Min. 6' Max. 5' Min.
E) 4' Min. 7' Max. 6' Min.
F) 5' Min. 8' Max. 7' Min.