EasyManuals Logo

Franklin Electric SubDrive Connect Plus SDCP-SUB2043 User Manual

Franklin Electric SubDrive Connect Plus SDCP-SUB2043
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
QUICKSTART GUIDE
Electrical Installation
3
Electrical Installation
Wiring Guidelines
1. Mount the drive as close as possible to the service entrance panel. Wire directly to the service entrance.
Do not connect to a sub-panel.
2. Use a dedicated branch circuit for the drive.
3. Route motor wiring out of the building as soon as possible. Separate input power and motor wiring by
at least 8 in. (20.3 cm).
4. Cross over other branch circuits and facility wiring at a 90 angle. If it is necessary to run wiring in par-
allel, separate by at least 8 in. (20.3 cm).
5. All control wiring—sensors, switches, transducers, etc.—should be in a separate conduit routed individ-
ually, not parallel, from high voltage wiring. In addition, any shielded cables should be properly
grounded.
Fuse/Circuit Breaker and Wire Sizing
Verify that the dedicated branch circuit for the drive is equipped with a properly-sized circuit breaker.
1
Based on a 3% voltage drop.
Maximum Motor Cable Length
1
Based on a 5% voltage drop.
NOTE: Flat-jacketed submersible motor cable is recommended. Cable lengths shown are for the highest
power motor supported.
Risk of damage to VFD
, or malfunction can occur.
Follow all wire routing and grounding instructions carefully. Inductive currents caused by parallel wiring,
or close proximity between high voltage and control wiring can cause unexpected behaviors.
Do not run input power and motor wires in the same conduit.
Do not run motor wires from multiple VFDs in common conduit.
Do not run control wiring parallel with high voltage wiring.
Do not install a magnetic contactor or disconnect in the motor circuit.
Do not run VFD wiring parallel with house or out-building wiring.
Do not use aluminum wires for VFD connections.
Do not use with a Ground Fault Circuit Interrupter (GFCI).
All wiring must comply with the National Electrical Code and local codes.
Improper splicing or damage to motor cable insulation may expose the conductor(s) to moisture and
can produce motor cable failure.
For retrofit application, make sure to check the integrity of power and motor leads. This requires
measuring the insulation resistance with a suitable megohm-meter.
Model
Input
Volts
Rated
Input
Amps
Fuse or
Breaker
Amps
AWG Copper Wire Sizes, 90° C Insulation, and Panel to Drive Cable Lengths (in feet)
1
10 8 6 4 3 2 1 1/0 2/0
SDCP-SUB2043
460 V 42 A 50 A 281 417 639 969 1172 1433 1711 2041 2443
SDCP-SUB1023
230 V 46 A 50 A 124 185 284 432 523 640 766 916 1098
Model
Output
Volts
Rated
Output
Amps
AWG 600V Copper Wire Sizes, 90° C Insulation, and Motor Cable Lengths (in feet)
1
10 8 6 4 3 2
SDCP-SUB2043
460 V 30 A 410 650 1030
SDCP-SUB1023
230 V 32.5 A 190 310 490 760 950 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Franklin Electric SubDrive Connect Plus SDCP-SUB2043 and is the answer not in the manual?

Franklin Electric SubDrive Connect Plus SDCP-SUB2043 Specifications

General IconGeneral
BrandFranklin Electric
ModelSubDrive Connect Plus SDCP-SUB2043
CategoryDC Drives
LanguageEnglish

Related product manuals