14
Electrical
Input Voltage 3-Phase 190-600 VAC
Frequency 50 Hz or 60 Hz
Motor SF (Max) Amps Range 3 amps to 359 amps
Maximum Conductor Size Through
Sensors
0.920” (23mm) Diameter Max
Measurement Accuracy
Voltage 1% ± 1 digit
Current 1% ± 1 digit
Trip Time
Overload, underload, overheat,
unbalance, overvoltage, undervoltage
3 seconds
Input Current, L1, L2, L3 0.15 amps
Control Circuit Rating 1.5 amps AC, up to 600 volts
Signal Circuit Rating
1 amp AC, up to 250 volts
Incandescent lamp, 100 watts max
Agency Approvals
UL 508 classi cation NKCR le E160632
cUL
Standards Met
Surge ANSI/IEEE C62.41
Electrical Fast Transient IEC 1000-4-4 Level 4, 4kV
ESD IEC 1000-4-2 Level 3, 6kV
Mechanical
Dimensions (WxHxD)
Base Unit 8.0” x 5.35” x 4.3” (20.3 x 13.6 x 10.9 cm)
Display Unit 7.0” x 3.0” x 1.4” (17.8 x 7.6 x 3.6 cm)
Total Unit 8.0” x 5.35” x 5.7” (20.3 x 13.6 x 14.5 cm)
Weight
Base Unit 46 oz (1.3 kg)
Display Unit 7 oz (0.2 kg)
Total Unit 53 oz (1.5 kg)
Operating Temperature Range -20°C to +60°C
Storage Temperature Range -30°C to +80°C
Relative Humidity 10-95% non-condensing
Protection Class
Display Unit NEMA 3R
Base Unit NEMA 1