EasyManua.ls Logo

Friedrich FPWC1 - Page 117

Friedrich FPWC1
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
117 PB
CORRECTION FACTORS
Piping Length Correctiion Factor
5(-15) 14( -10) 23( -5) 32(0) 44.6(7)
OUTDOOR TEMPERATURE
50(10) 59(15)
Correction factor(humidity rate 85% RH) 0.95 0.95 0.9 2 0.8 4 1.0 1.0 1.0
Correction Factor
NOTE:
Correction factors according to defrosting operation
The heating capacity in the preceding paragraph excludes the condition of the frost or the
or the defrosting operation period. In consideration of the frost or the defrosting operation,
the heating capacity is corrected by the equation below.
Corrected heating capacity = Defrost Correction factor x unit capacity
[°F(°C) DB]
Correction Factor is not valid when the outdoor unit is covered or encapsulated with snow.

Table of Contents

Other manuals for Friedrich FPWC1

Related product manuals