174 PB
COMPONENTS TESTING
Field Settings (ESP Setting) Duct Type Only
Model
Btu/h)
(Capacity
static pressure
The range of
9K/12K/18K
Function code set
0-0.015 in.Hg
(0-50Pa)
0-50, more than 50 is
0.015 in.Hg (50 Pa),
[default: 0 (0 in.Hg or 0Pa)]
Static pressure setting:
Hold down both“MODE”button and“ADD.FUNC.”button for 3 seconds, symbol and parameter code
blinking at the same time.
Press“ / ”button to adjust parameter number until display “17”, and press “ENTER”button to entering
system parameter adaption state, symbol stop blinking.
Select desired parameter code 10 by pressing “ / ” button , and press "ENTER" button to confirm.
Select desired function code to rewrite the parameter values by pressing “ / button , and press
"ENTER" button to confirm.
Press “ON/OFF”button or “CANCEL”button to quit.
Error Indicator
Parameter Code
Function Code
LCD
1
2
3
4
5
The static pressure can be freely adjusted by using specific wire remote controller.
YXE-C01U(E)/YXE-C02U(E)