Basepan Heater
Basepan Heat Thermostat
VRP model numbers that end with the ‘L’ character will come equipped with a basepan heater. The outdoor tem-
perature at which the basepan heat engages can be set via an analog thermostat. The “MIN” setting will turn on the
basepan heat at 0F outdoor ambient. The “MAX” setting will turn on the basepan heat at 50F outdoor ambient. Units
ship from the factory with the thermostat set to turn on the basepan heat at 15F outdoor ambient.
There is a 3F hysteresis on the set point.