4
General Specications
Nomenclature
V R P 2 4 K 2 5 S S A S -A
Series
VRP Heat Pump
Engineering Code
S= Standard
L= Basepan Heat
Nominal Capacity (Btu /Hr.)
12 = 4000 - 16000 Operating Range
24 =12,000 - 28000 Operating Range
Plenum and Louver Configuration
A= Compact (VRP12 Only)
B= Standard
Voltage
K = 230/208 V
R = 265 V
Heater Watts
25 = 2.5 kW
34 = 3.4 kW
50 = 5.0 kW
75 = 7.5 kW
10 = 10.0 kW
ALL VRP MODELS
VRP24 ONLY
S= Standard
R= Reheat
Outdoor Air/ Ventilation
S= Standard No FreshAire™
F= Single OA Fan 35 CFM
D= Dual OA Fans 70 CFM
Model VRP12K / VRP12R VRP24K / VRP24R
Cooling Performance Data (Cooling Standards: 95°F DB/75°F WB outdoor, 80°F DB/67°F WB indoor)
Voltage 230/208 265 230/208 265
Cooling Btu (Rated) 12000 23525
Cooling Btu (Min. - Max) 5400 - 16000 14500 - 28000
Outdoor Operating Range (°F ) 55 - 115 55 - 115
Power (W) 923 2138
SEER 20.0 17.5
EER 13.0 11.0
Sensible Heat Ratio 0.7 0.7
Cooling Amps 4.3 10.0
Heat Pump Performance Data
Voltage 230/208 265 230/208 265
Heating Btu ( Rated @ 47° F ) 11500 21000
Heating Btu ( @ 17° F ) 7700 13000
Heating Btu (Min. - Max.) 4000 - 14000 12000 - 26000
Heat Pump Outdoor Operating Range (°F ) 0 - 70 0 - 70
HSPF 10.0 10.0
Heating Power (W) 991 1954
Heat Pump Amps 4.8 4.1 9.1 7.8