EasyManua.ls Logo

Fronius Primo GEN24 3.6 - Page 170

Fronius Primo GEN24 3.6
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DC input data
Insulation resistance test limit value
between module array and earth (on
delivery)
10)
100 kΩ
Adjustable range of insulation resist-
ance test between module array and
earth
9)
10 - 10 000 k
Limit value and tripping time of the
sudden residual current monitoring
(on delivery)
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
Limit value and tripping time of the
continuous residual current monitor-
ing (on delivery)
300 / 300 mA / ms
Adjustable range of continuous resid-
ual current monitoring
9)
30 - 300 mA
Cyclic repetition of the insulation res-
istance test (on delivery)
24 h
Adjustable range for the cyclic repeti-
tion of the insulation resistance test
-
DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output 3 680 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 3 680 W
Max. output power 3 680 W
Rated apparent power 3 680 W
Nominal mains voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 23.7 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Initial short circuit current / phase I
K
23.7 A
Total harmonic distortion < 2 %
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
at PCC
4)
None
170

Table of Contents

Related product manuals