General data
Sound pressure 42 dB(A) (ref. 20µPa)
Safety class (according to IEC62103) 1
Protection devices
DC isolation measurement Warning / shutdown at R
ISO
<
100 kOHM
Overload performance Operating point shift, power limiter
DC disconnector Integrated
RCMU Integrated
RCMU classification The software class of the safety plat-
form(s) is specified as a class B con-
trol function (single channel with peri-
odic self-test) according to IEC60730
Annex H.
Active anti-islanding method Frequency conversion method
Data communication
WLAN SMA-RP connection
(FCC ID: QKWPILOT01 / IC ID:
12270A-PILOT01)
802.11b/g/n (WPA, WPA2)
Frequency: 2.4 GHz
Ethernet (LAN) RJ45, 10/100 MBit
Wired shutdown (WSD) max. 28 devices/WSD chain
max. distance between two devices =
100 m
Modbus RTU SunSpec (2x) RS485 2-wire
Voltage level of digital inputs low: min. 0 V - max. 1.8 V
high: min. 4.5 V - max. 28.8 V
Input currents of digital inputs depending on the input voltage;
input resistance = 70 kOhm
Total power for digital output
(internal supply)
6 W at 12 V (USB not connected)
Power per digital output
(external supply)
1 A at >12.5 V-24 V
(max. 3 A in total)
Datalogger/web server Integrated
Fronius Primo
GEN24 4.0 / 4.0
Plus
DC input data
MPP voltage range
(at rated power)
210 - 530 V
Max. input voltage
at 1000 W/m²/-10°C in an open circuit
600 V
Min. input voltage 65 V
Feed-in start-up input voltage in grid
operation
5)
80 V