DC input data
Max. inverter backfeed current to the
array
3)
PV 1
PV 2
36 A
19 A
Number of inputs - PV 1 2
Number of inputs - PV 2 2
Max. capacity of the module array
against earth
1 000 nF
Insulation resistance test limit value
between module array and earth (on
delivery)
10)
100 kΩ
Adjustable range of insulation resist-
ance test between module array and
earth
9)
10 - 10 000 k
Limit value and tripping time of the
sudden residual current monitoring
(on delivery)
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
Limit value and tripping time of the
continuous residual current monitor-
ing (on delivery)
300 / 300 mA / ms
Adjustable range of continuous resid-
ual current monitoring
9)
30 - 300 mA
Cyclic repetition of the insulation res-
istance test (on delivery)
24 h
Adjustable range for the cyclic repeti-
tion of the insulation resistance test
-
DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output 5 000 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 5 000 W
Max. output power 5 000 W
Rated apparent power 5 000 W
Nominal mains voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 27.5 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
180