EasyManua.ls Logo

Fronius Primo GEN24 3.6 - Page 184

Fronius Primo GEN24 3.6
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DC input data battery
Min. voltage 150 V
Max. current 22 A
Max. output 6 000 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 6 000 W
Max. output power 6 000 W
Rated apparent power 6 000 W
Nominal mains voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 27.5 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Initial short circuit current / phase I
K
27.5 A
Total harmonic distortion < 2 %
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
at PCC
4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4 133 W (for 5 s)
Rated power 3 000 W
Nominal output current 13 A
Nominal mains voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 8 268 W (for 5 s)
Rated power 6 000 W
Nominal output current 26.1 A
Nominal mains voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
184

Table of Contents

Related product manuals