The permissible operating position of
the device is horizontal.
The ambient air surrounding the device must be kept free from battery acid va-
pors. Mounting the device directly above the battery to be charged should there-
fore be avoided.
Cooling air
The device must be set up so that cooling air can flow through the housing open-
ings provided unhindered. There must always be a minimum distance of 0.2 m
(7.874 in.) from the air inlet and outlet openings. The ambient air must be free
from
-
Excessive dust exposure
-
Electrically conductive particles (carbon black or metal chips)
-
Heat sources
The cooling air flows in and out as indicated by the arrow symbols in the follow-
ing illustrations.
NOTE!
Danger due to partially or completely covered air intake and outlet openings.
This can result in damage to property.
▶
The setup of several devices one behind the other should be staggered.
If the devices are arranged in a line one behind the other without being
staggered, the distance between the devices must be as follows:
a)
8 kW: Minimum distance 30 cm (11.81 in.)
b)
16-18 kW: Minimum distance 60 cm (1 ft. 11.62 in.)