Insulation (EN IEC 62052-11, EN IEC 62053-21)
Insulation voltage 4 kVAC RMS (1min)
Electromagnetic compatibility
Emission test In acc. with EN IEC 62052-11, EN
50470-3
Immunity test In acc. with EN IEC 62052-11, EN
50470-3
Operating conditions
Reference temperature 25 °C (±5 °C)
Operating range -25 bis +55 °C
Temperature limit for storage and trans-
port
-30 to +80 °C
Mechanical environment
Electromechanical environment
M2
E2
Housing
Housing 3 modules according to DIN 43880
Sealable housing/terminal cover
Connection Screw connection
Mounting Can be snapped onto 35 mm DIN rail
Housing material Noryl, self-extinguishing
Degree of protection (EN 60529) IP51 housing, IP20 connections
Weight 240 grams
Terminals
Measuring input
Wire Min. 1 mm² / max. 16 mm²
Recommended torque max. 2.8 Nm
Data output
Wire min 0.05 mm²
Recommended torque max. 0.4 Nm
Fronius manufac-
turer's warranty
Detailed, country-specific warranty terms are available on the internet:
www.fronius.com/solar/warranty
To obtain the full warranty period for your newly installed Fronius inverter or storage sys-
tem, please register at: www.solarweb.com.