V outer limit MIN
adjustable
60–126 0.016–21.0
1–1260
60–126 0.016–21.0
1–1260
V outer limit MAX
adjustable
128–166 0.016–21.0
1–1260
128–166 0.016–21.0
1–1260
Setup 220/Setup 220N Setup BR N/Setup BR
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
Setup 50 HZ/Setup 50 HN
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 64 0.16
8
V inner limit min 112 2
100
V outer limit max 139 1
50
V inner limit max 152 0.16
8
V outer limit MIN
adjustable
60–132 0.02–21.0
1–1050
V outer limit MAX
adjustable
128–166 0.02–21.0
1–1050
400–480 setups
Setup 440N Setup 480N
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 127 0.16
9
139 0.16
9
V inner limit min 225 2
118
244 2
118
V outer limit max 280 1
58
305 1
58
V inner limit max 305 0.16
9
332 0.16
9
V outer limit MIN
adjustable
120–252 0.016–21.0
1–1260
120–275 0.016–21.0
1–1260
V outer limit MAX
adjustable
256–332 0.016–21.0
1–1260
279–332 0.016–21.0
1–1260
Setup 50HN Setup HI3
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 120 0.16
8
139 0.5
28
V inner limit min 211 2
100
244 21
1258