EasyManua.ls Logo

Fronius Symo 10.0-3 208-240 - Field Adjustable Trip Points

Fronius Symo 10.0-3 208-240
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
Field Adjustable Trip Points
208–240 setups
Setup 208/Setup 208N Setup 240/Setup 240N
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 60 0.16
9
69 0.16
9
V inner limit min 106 2
118
122 2
118
V outer limit max 132 1
58
152 1
58
V inner limit max 144 0.16
9
166 0.16
9
V outer limit MIN
adjustable
60–119 0.016–21.0
1–1260
60–137 0.016–21.0
1–1260
V outer limit MAX
adjustable
121–166 0.016–21.0
1–1260
140–166 0.016–21.0
1–1260
Setup HI1 Setup HI2
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 69 0.5
28
60 0.16
28
V inner limit min 122 21.0
1258
106 21.0
1258
V outer limit max 152 1
58
132 1
58
V inner limit max 166 0.16
9
144 0.16
9
V outer limit MIN
adjustable
60–137 0.016–21.0
1–1260
60–119 0.016–21.0
1–1260
V outer limit MAX
adjustable
140–166 0.016–21.0
1–1260
121–152 0.016–21.0
1–1260
Setup 220/Setup 220N Setup BR N/Setup BR
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 64 0.16
9
102 0.4
24
V inner limit min 112 2
118
102 0.4
24
V outer limit max 139 1
58
139 0.2
12
V inner limit max 152 0.16
9
139 0.2
12

Table of Contents