40
Field Adjustable Trip Points
208–240 setups
Setup 208/Setup 208N Setup 240/Setup 240N
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 60 0.16
9
69 0.16
9
V inner limit min 106 2
118
122 2
118
V outer limit max 132 1
58
152 1
58
V inner limit max 144 0.16
9
166 0.16
9
V outer limit MIN
adjustable
60–119 0.016–21.0
1–1260
60–137 0.016–21.0
1–1260
V outer limit MAX
adjustable
121–166 0.016–21.0
1–1260
140–166 0.016–21.0
1–1260
Setup HI1 Setup HI2
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 69 0.5
28
60 0.16
28
V inner limit min 122 21.0
1258
106 21.0
1258
V outer limit max 152 1
58
132 1
58
V inner limit max 166 0.16
9
144 0.16
9
V outer limit MIN
adjustable
60–137 0.016–21.0
1–1260
60–119 0.016–21.0
1–1260
V outer limit MAX
adjustable
140–166 0.016–21.0
1–1260
121–152 0.016–21.0
1–1260
Setup 220/Setup 220N Setup BR N/Setup BR
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V
AC
[V] Clearing Time [s]
Clearing Time [p]
V outer limit min 64 0.16
9
102 0.4
24
V inner limit min 112 2
118
102 0.4
24
V outer limit max 139 1
58
139 0.2
12
V inner limit max 152 0.16
9
139 0.2
12