EasyManua.ls Logo

Fronius Symo 12.0-3 208-240 - Connecting the Inverter to the Public Grid (AC); Safety; Permitted Cables

Fronius Symo 12.0-3 208-240
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Connecting the inverter to the public grid (AC)
Safety
Permitted Cables AC cables with the following design can be connected to the AC terminals of the inverter:
WARNING! An electric shock can be fatal. Inadequately sized electrical compo-
nents can cause serious injury and damage to property.
- All electrical connections must be made in accordance with the National
Electrical Code, ANSI/NFPA 70, and any other regulations applicable to the
installation site.
- Installations in Canada must be carried out in accordance with applicable Ca-
nadian standards.
- Use min.194°F (90°C) copper wire for all grounding wires (see NEC table
250.122).
- Voltage drop and other considerations may mean larger cable cross sections
need to be used.
- Use only solid or stranded wire. Do not use fine stranded wire.
CAUTION! Danger of damaging the inverter due to improperly connected termi-
nals. Improperly connected terminals can cause thermal damage to the inverter
and may cause a fire. When connecting the AC and DC cables, make sure that
all terminals are tightened securely using the proper torque.
NOTE! When connecting aluminum cables:
- follow all national and international guidelines regarding the connection of
aluminum cables
- follow the instructions of the cable manufacturer
- perform an annual check to ensure that the cables are firmly attached ac-
cording to the proper torque.
NOTE! Form a min. 4 in. cable loop with all cables.
NOTE!
- Make sure that the grid neutral conductor is grounded. For insulated net-
works (without grounding), this is not the case, and operation of the inverter
is not possible.
- A neutral conductor is required for measurement purposes when operating
the inverter. The neutral conductor must have a current carrying capacity of
at least 1 A.
- Copper (Cu) or aluminum (Al): round, solid
- Copper: round, stranded, up to conductor class 4
Cu / Al Cu
AC & DC = copper cables (Cu)
The following wire combinations can be used for wiring.
Select a sufficiently large cable cross-section based on the actual device output!
AWG
round
AWG
strand
ed
AWG
stranded/round
AWG
round/round
AWG
stranded/stranded
4
2)
6
2)
6/6
4)
6/12
2)
6/14
2)
6/16
3)
8
2)
8
1)
8/10
1)
8/12
1)
8/14
1)
8/12
2)
8/10
2)
8/12
1)
8/14
1)
8/16
3)

Table of Contents

Other manuals for Fronius Symo 12.0-3 208-240

Related product manuals