If DC cables are laid over the shaft of the
DC main switch or across the DC main
switch connection block, the cables may be
damaged when the inverter is pivoted or the
inverter may not be able to be pivoted.
IMPORTANT! Do not lay DC cables over
the shaft of the DC main switch or across
the DC main switch connection block!
6-21 mm² / 10-4 AWG / Al/Cu
5.5 Nm / 48.6 lbf.in
option
DC+
DC-
42,0201,4479
42,0201,4479
42,0201,4480
42,0201,4480
10.0-3, 12.0-3 208-240 / 10.0-3, 12.5-3 480 max. 41,5 A
15.0-3, 17.5-3, 20.0-3, 22.7-3, 24.0-3 480 max 51 A
12x 1.8 Nm / 16 lbf.in
BASIC
MPP TRACKER 2
OFF
3
16 lbf.in / 1.8 Nm
4
1
2
1
DC = (+)DC = (-)
2
DC =
5
10.0-3 - 12.0-3 208-240
U
DC max
0 - 11154 ft.
(0 - 3400 m)
ft. (m)
600 V
1000 V
0 - 6561 ft.
(0 - 2000 m)
> 8202 - 9842 ft.
(> 2500 - 3000 m)
> 6561 - 8202 ft.
(> 2000 - 2500 m)
> 9842 - 11154 ft.
(> 3000 - 3400 m)
950 V
900 V
850 V
U
DC max
ft. (m)
10.0-3 - 24.0-3 480
6