121
EN-US
Documentation
Documentation - The electrician who carried out the inspections is responsible for documenting them
correctly
- All inspections carried out are to be documented in an inspection log. The measured
values as well as the inspection equipment used, and calibration data must be given
- If an individual inspection cannot be carried out, reasons for the inspector's decision
are to be documented
- If the inspection is not passed, then the device in question must be clearly identified
as unsafe and the operator must be informed. The equipment must no longer be op-
erated.
The "Safety Inspection" inspection log can be found on the Fronius Partnerweb.