9-22
Name Command
type
character
Function type
character and
number
Data and operation
Failure description;
current one
R M16
Failure description;
previous one
R M17
Failure description;
one before previous
one
R M18
Failure description;
one before two
previous ones
R M19
Refer to (4) Alarm display data
Total operation time
R M20
0 to 65535 / 0 to 65535 hours
DC link voltage
monitor
R M21
0 to 500 / 0 to 500V (200V class)
0 to 1000 / 0 to 1000V (400V class)
Function code R M23
4112H = E11S single-phase 200V
4113H = E11S 3-phase 200V
4114H = E11S 3-phase 400V
Capacity code R M24 1=0.01kW
ROM version R M25 0 to 99: Standard, > 100: Non-standard
Transmission error
handling code
R M26
Refer to section 9-4-9. The latest error is
returned. The communication error is initialized
when the power is turned off.
Main circuit
capacitor life
R M46 1=0.1%
Cooling fan life R M48 1 = 1 hour
Note)
1) Output frequency monitoring (M09, M35) adds an ASCII code for forward rotation (space), reverse
rotation (minus) and stop (space) as direction of rotation data, and handled as 5-byte data.