5-6
P: Motor parameters
Function code
Name Setting range
Min.
unit
Factory
setting
RS485
Data
format
User setting
P01
Number of motor 1
poles
2 to 14 2 4
X
0
P02
Motor1 (Capacity)
0.01 to 5.5kW (4.0kW or less)
0.01 to 11.00kW(5.5/7.5kW)
0.01kW
Nominal
applied
motor kW
X
4
P03
(Rated current)
0.00 to 99.9A 0.01A
Fuji's
standard
rating
X
6
P04
(Tuning)
0: Inactive
1: Active (%R1, %X)
2: Active (%R1, %X, Io)
1 0
X
12
P05
(Online tuning)
0: Inactive
1: Active
1 0
X
0
P06
(No-load current)
0.00 to 99.9A
0.01A
Fuji's
standard
rating
X
6
P07
(%R1 setting)
0.00 to 50.00%
0.01%
Fuji's
standard
rating
4
P08
(%X setting)
0.00 to 50.00%
0.01%
Fuji's
standard
rating
4
P09
control 1)
0.00 to 15.00Hz
0.01Hz
0.00
4
P10
response time 1)
0.01 to 10.00s
0.01s 0.50
4
Description of change during operation
: The data changed by the or key takes effect on the inverter operation. However, press the
key to store the new data.
: Press the or key to change the data. The new data takes effect after the key is pressed to
store the data.
X
: The data can be changed only while the inverter is stopped.