MICREX-F Series SIO Driver
GP-Pro EX Device/PLC Connection Manual
12
Setting of External Device
Turn ON the DIP switch No.8 "Initialization method" on the rear panel of general-purpose interface module of the
External Device. When you perform the settings with the switch, the head code, end code and send condition will
be fixed. Use the rotary switch for MODE setting. When you select MODE2 or 3, use the rotary switch to specify
the same number as the station No. in the device setting. The setting is not necessary for MODE1 (RS232C 1:1
connection). Please refer to the connection configuration diagrams for more details.
No. Setup Items Setup Description
1OFF
Baud rate = 192002ON
3ON
4OFF Stop bit length = 2
5ON Data bit length = 7
6ON Parity bit = Even
7ON Parity bit = Enable
8ON Switch setting effective
Setup Items Setup Description Notes
MODE switch
Depending on
connection type
Set by the rotary switch
Station No.
Depending on
connection type
Send Condition None
FixedHead Code :
End Code CR/LF