– 3 –
3
Installation and Mounting
3-1
External/Panel Cut Dimensions
Caution
Panel cut dimensions should also meet the above dimensions after the panel
is coated.
Cautions when Close Fit Mounting:
When the power supply is AC 200V, keep the maximum ambient temperature
at 45°C. For vertical close-fit mounting, use a power source of AC 100V. (In
both cases, a fan is recommended as a measure against radiation.)
When there is an instrument larger than 70 mm or a wall to the right of
the controller, move it as least 30 mm away.
Cautions when wiring:
Start by wiring from the left-hand terminals (terminals 1 to 12).
Use a screw that is the right size on terminals and tighten them with a
torque of about 0.8 N/m.
Do not attach anything to unused terminals. (Do not use relay terminals.)
PC loader interface
PXG9
TOP
TOP
13-2437-48 61-7249-60
1-12
25-36
waterproof packing
panel
terminal screw M3
96
96
79.510
2
91.5
115.5 MAX
t
6.2
31
32
33
34
35
36
7
8
9
1
2
3
4
5
6
10
11
12
mounting fixture
(fastening torque 0.15 N•m)
25
26
27
28
29
30
Panel thickness
1 to 8 mm
PC loader interface
25-36
1-12
13-24
Waterproof packing
panel
terminal
screw M3
48
96
Mounting fixture
(fastening torque 0.15 N•m)
PXG5
7810
2
91.5
115.5 MAX
t
Panel thickness
1 to 8 mm
6.2
12
11
10
36
35
34
33
32
31
9
8
7
6
5
4
3
2
1
25
26
27
28
29
30
Installing multiple controllers
Installing multiple controllers horizontally
(In this installing, the waterproof of PXG is lost.)
50 MIN.
45
92
+0.6
0
116 MIN.
+0.8
0
(48 × n–3)
+0.8
0
+0.8
0
92
Installing multiple controllers
92
+0.8
0
92
+0.8
0
116 MIN.
100 MIN.