3-6
3.3 Running Mode
When the inverter is turned on, it automatically enters Running mode in which you can:
(1) Monitor the running status (e.g., output frequency and output current),
(2) Configure the reference frequency and PID commands, etc.,
(3) Run/stop the motor,
(4) Switch between remote and local modes
(5) Switch the operation from the keypad to the one by external signals (terminal block), and
(6) Monitor light alarms
3.3.1 Monitoring the running status
In Running mode, the items listed below can be monitored. Immediately after the inverter is turned on, the
monitor item specified by the display item selection function*
1
is displayed. Press the key to switch
between monitor items.
*1 Function code K10 for the FRENIC-HVAC/AQUA series
Function code E43 for the FRENIC-Ace series
Table 3.4 Monitoring Items (Selectable anytime)
Monitor names
Sub-
monitor
Unit Meaning of displayed value
HVAC/
AQUA
Ace
Function code data
K10 E43
Speed monitor
The speed monitor selection function*
2
specifies what to be displayed on
the main monitor.
0 0
Output frequency Fout1 Hz
Frequency (before slip compensation)
actually being output
Y Y (K11 = 1) (E48 = 0)
Output frequency
(primary)
Fout2 Hz
Frequency (after slip compensation)
actually being output
Y Y (K11 = 2) (E48 = 1)
Reference
frequency
Fref Hz Reference frequency being set Y Y (K11 = 3) (E48 = 2)
Motor speed Sync r/min
P01
120
x(Hz)frequency Output
Y Y (K11 = 4) (E48 = 3)
Load shaft speed Load r/min
Output frequency (Hz) K30 Y - (K11 = 5)
Output frequency (Hz) E50 - Y (E48 = 4)
Line speed Line m/min
Output frequency (Hz) K30 N - -
Output frequency (Hz) E50 - Y (E48 = 5)
Constant feeding
rate time
Feed min
E39x(Hz)frequency Output
E50
N Y - (E48 = 6)
Speed (%) SPD %
100x
frequency Maximum
frequency Output
Y Y (K11 = 8) (E48 = 7)
Output current Iout A Current output from the inverter in RMS Y Y 13 3
Output voltage Vout V Voltage output from the inverter in RMS Y Y 14 4
Calculated torque TRQ %
Motor output torque in %
(Calculated value)
Y Y 18 8
Input power PWR kW Input power to the inverter Y Y 19 9
PID command
(final) (Note 1)
SV J105
PID command and its feedback
converted into physical quantities of the
object to be controlled.
The display unit can be selected with
Function code J105.
N Y - 10
PID feedback value
(Note 1)
PV J105 N Y - 12
*2 Function code K11 for the FRENIC-HVAC/AQUA series
Function code E48 for the FRENIC-Ace series