3-7
ENGLISH
Table 3.4 Monitoring Items (Selectable anytime) (Continued)
Monitor names
Sub-
monitor
Unit Meaning of displayed value
HVAC/
AQUA
Ace
Function code data
K10 E43
Timer count in
seconds
(Note 2)
Timer s
Remaining time for the timer operation
enabled.
N Y - 13
PID output (Note 1) MV %
PID output in %, assuming the maximum
frequency (F03) as 100%
N Y - 14
Load factor LOF %
Load factor of the motor in % as the
rated output being at 100%
Y Y 25 15
Motor output MPW kW Motor output in kW Y Y 26 16
Analog input
monitor (Note 3)
AMon
Unit
specified
for each
terminal
Shows an analog input to the inverter in
a format suitable for a desired scale.
Refer to the function codes below.
Terminal [12]: C59, C60
Terminal [C1]: C65, C66
Terminal [V2]: C71, C72
Y Y 27 17
Current position
pulse (Note 4)
P.PLS pulse
Shows the current position pulse for
positioning control.
N Y - 21
Position deviation
pulse (Note 4)
d.PLS pulse
Shows the position deviation pulse for
positioning control.
N Y - 22
Torque current
(Note 5)
TRQI %
Shows the torque current command
value or calculated torque current.
N Y - 23
Exciting current
magnetic flux
command
(Note 5)
Flux %
Shows the magnetic flux command
value.
N Y - 24
Input watt-hour Wh
Input watt-hour (kWh)
100
Refer to function code K31 for details. Y - 35
Refer to function code E51 for details. - Y 25
(Note 1) These items appear when J01 (PID control) 0. The , which indicates that the internal PID is
selected, is displayed on the status icon field.
(Note 2) This item appears only when timer operation is enabled (Function code C21).
(Note 3) The analog input monitor appears only when it is assigned to terminal [12], [C1] or [V2] with any of
E61 to E63 (data = 20). Specify the display unit with C58, C64 or C70.
(Note 4) These items appear only when positioning control is enabled, e.g., by assigning the S/R function
("Start/reset") to any input terminal.
(Note 5) These items appear only when vector control is enabled (Function code F42).