EasyManua.ls Logo

Fuji Electric TP-A1 - Page 21

Fuji Electric TP-A1
35 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-8
The following monitor items appear only when the related PID control or external PID control is enabled. Items
being disabled cannot be displayed.
Table 3.5 Monitoring Items (Selectable when PID control or external PID control is enabled)
Monitor names
Sub-
monitor
Unit Meaning of displayed value
HVAC/
AQUA
Ace
Function
code data
for K10,
E43
PID command (Note 6) SV
J105
J205
PID command and its feedback converted into
physical quantities of the object to be controlled.
The display unit can be selected with Function
code J105 or J205.
Y N 50
PID feedback value
(Note 6)
PV
J105
J205
Y N 51
PID output (Note 6) MV %
PID output in %, assuming the maximum
frequency (F03) as 100%
Y N 52
PID control 1 command
(Note 7)
SV1 J105
PID control 1 command and its feedback
converted into physical quantities of the object to
be controlled.
The display unit can be selected with Function
code J105.
Y N 53
PID control 1 feedback
value
(Note 7)
PV1 J105 Y N 54
PID control 2 command
(Note 7)
SV2 J205
PID control 2 command and its feedback
converted into physical quantities of the object to
be controlled.
The display unit can be selected with Function
code J205.
Y N 55
PID control 2 feedback
value
(Note 7)
PV2 J205 Y N 56
External PID control 1
command (final)
(Note 8)
E. SVF
J505
J605
PID command and its feedback converted into
physical quantities of the object to be controlled.
The display unit can be selected with Function
code J505 or J605.
Y N 60
External PID control 1
feedback value (final)
(Note 8)
E. PVF
J505
J605
Y N 61
External PID control 1
output (Note 8)
E. MV1 %
External PID output in %, assuming the PID
output as 100%
Y N 62
External PID control 1
manual command
(Note 9)
E. MU1 %
External PID manual command in %, assuming
the manual command value as 100%
Y N 63
External PID control 1
command (Note 10)
E. SV1 J505
PID command and its feedback converted into
physical quantities of the object to be controlled.
The display unit can be selected with Function
code J505.
Y N 64
External PID control 1
feedback value
(Note 10)
E. PV1 J505 Y N 65
External PID control 2
command (Note 11)
E. SV2 J605
PID command and its feedback converted into
physical quantities of the object to be controlled.
The display unit can be selected with Function
code J605.
Y N 70
External PID control 2
feedback value
(Note 11)
E. PV2 J605 Y N 71
External PID control 2
output (Note 11)
E. MV2 %
External PID output in %, assuming the PID
output as 100%
Y N 72
External PID control 2
manual command
(Note 12)
E. MU2 %
External PID manual command in %, assuming
the manual command value as 100%
Y N 73

Related product manuals