OUTDOOR UNIT
INDOOR UNIT
8-4. SAFETY DEVICE
AB A18 / 24 / 36 / 45 L
Circuit protection Current fuse (PCB)
Fan motor protection Thermal protection program
140±20°C OFF
110±20°C ON
Protection form
Model
3.15A 250V
AO A18L AO A24L
Fan motor protection Thermal protection program
OFF:100
+15
-10
°C
ON:95
+15
-10
°C
OFF:110
+15
-10
°C
ON:105
+15
-10
°C
Thermal protection program (COMPRESSR TEMP.)
Thermal protection program (DISCHARGE TEMP.)
15A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF:110°C
ON: After 40 minutes
OFF:110°C
ON: After 7 minutes
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTD CIRCUIT BOARD)
Protection form
20A 250V
5A 250V
Model
AO A36L AO A45L
Current fuse (NEAR THE TERMINAL)
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
Fan motor protection Thermal protection program
High Pressure Protection High Pressure Switch
Thermal protection program (COMPRESSOR TEMP.)
Thermal protection program (DISCHARGE TEMP.)
Protection form
25A 250V
10A 250V
Model
5A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF : 110°C
ON : 80°C
OFF : 115°C
ON : After 7 minutes
OFF : 130±20°C
ON : 100±20°C
OFF : 4.2±0.1MPa
ON : 3.2±0.15MPa