5-1. COOLING OPERATION
5-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2 °C higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5 °C lower than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2 °C to -2.5 °C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
minimum
frequency
maximum
frequency
AB*A18LATN 18Hz
18Hz
18Hz
18Hz
113Hz
113Hz
77Hz
77Hz
AB*A24LATN
AB*A36LATN
AB*A45LATN
Outdoor air
temperature
( Table 1 : Compressor Frequency Range )
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
05-01
5. DESCRIPTION OF EACH CONTROL OPERATION
AB*A18LATN A zone 113Hz 66Hz 54Hz 34Hz AB*A36LATN A zone
B zone 113Hz 66Hz 54Hz 34Hz B zone
C zone 80Hz 54Hz 45Hz 34Hz C zone
D zone 54Hz 45Hz 38Hz 24Hz D zone
E zone 54Hz 45Hz 38Hz 24Hz E zone
F zone 54Hz 45Hz 38Hz 24Hz F zone
AB*A24LATN A zone 113Hz 66Hz 54Hz 34Hz AB*A45LATN A zone 77Hz 48Hz 41Hz 31Hz
B zone 113Hz 66Hz 54Hz 34Hz B zone 77Hz 48Hz 41Hz 31Hz
C zone 80Hz 54Hz 45Hz 34Hz C zone 55Hz 41Hz 37Hz 31Hz
D zone 54Hz 45Hz 38Hz 24Hz D zone 41Hz 37Hz 33Hz 25Hz
E zone 54Hz 45Hz 38Hz 24Hz E zone 41Hz 37Hz 33Hz 25Hz
F zone 54Hz 45Hz 38Hz 24Hz F zone 41Hz 37Hz 33Hz 25Hz
Me Lo Qu
Fan speed mode
HiLo Qu
Fan speed mode
Hi Me
A zone