7. Additional charge calculation
7-1. Model: ASU9RL2
Refrigerant type R410A
Factory charge amount
lb oz 1 lb 7 oz
g 650
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge amount
oz 0 3.5
g 0 100
7-2. Model: ASU12RL2
Refrigerant type R410A
Factory charge amount
lb oz 1 lb 12 oz
g 800
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge amount
oz 0 3.5
g 0 100
- 35 -