- 198 -
OUTDOOR UNIT
AOU24RLXFZH
6-3. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Model: AOU24RLXFZH
• TC: Total Capacity, IP: Input Power
• The data is based on the following conditions:
Pipe length: 7.5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
Indoor units: 7,000 Btu
Indoor temperature
°FDB 60 65 70 75 78
°FDB °FWB
TC IP TC IP TC IP TC IP TC IP
kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW
-15 -17 5.63 0.84 5.50 0.86 5.37 0.88 5.23 0.89 5.10 0.91
-5 -7 7.97 1.03 7.78 1.05 7.59 1.07 7.40 1.09 7.21 1.12
5 3 10.31 1.22 10.06 1.24 9.82 1.27 9.57 1.30 9.33 1.32
14 12 10.50 1.22 10.25 1.24 10.00 1.27 9.75 1.29 9.50 1.32
23 19 10.69 1.22 10.44 1.24 10.18 1.27 9.93 1.29 9.67 1.32
32 28 11.21 1.04 10.95 1.06 10.68 1.08 10.41 1.10 10.15 1.12
41 37 11.60 1.00 11.33 1.02 11.05 1.04 10.77 1.06 10.50 1.08
47 43 11.99 0.98 11.71 1.00 11.42 1.02 11.14 1.04 10.85 1.06
50 47 12.28 0.98 11.99 1.00 11.70 1.02 11.40 1.04 11.11 1.06
59 50 13.00 0.98 12.69 1.00 12.38 1.02 12.07 1.04 11.77 1.06
68 59 13.84 0.98 13.51 1.00 13.18 1.02 12.85 1.04 12.52 1.06
75 65 14.68 0.98 14.33 1.00 13.98 1.02 13.63 1.04 13.28 1.06
Indoor temperature
°CDB 15.6 18.3 21.2 23.9 25.6
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-26.1 -27.0 1.65 0.84 1.61 0.86 1.57 0.88 1.53 0.89 1.49 0.91
-20.6 -21.7 2.34 1.03 2.28 1.05 2.23 1.07 2.17 1.09 2.11 1.12
-15.0 -16.1 3.02 1.22 2.95 1.24 2.88 1.27 2.81 1.30 2.73 1.32
-10.0 -11.1 3.08 1.22 3.00 1.24 2.93 1.27 2.86 1.29 2.78 1.32
-5.0 -7.2 3.13 1.22 3.06 1.24 2.98 1.27 2.91 1.29 2.83 1.32
0.0 -2.2 3.29 1.04 3.21 1.06 3.13 1.08 3.05 1.10 2.97 1.12
5.0 2.8 3.40 1.00 3.32 1.02 3.24 1.04 3.16 1.06 3.08 1.08
8.3 6.1 3.52 0.98 3.43 1.00 3.35 1.02 3.26 1.04 3.18 1.06
10.0 8.3 3.60 0.98 3.51 1.00 3.43 1.02 3.34 1.04 3.26 1.06
15.0 10.0 3.81 0.98 3.72 1.00 3.63 1.02 3.54 1.04 3.45 1.06
20.0 15.0 4.06 0.98 3.96 1.00 3.86 1.02 3.77 1.04 3.67 1.06
23.9 18.3 4.30 0.98 4.20 1.00 4.10 1.02 4.00 1.04 3.89 1.06