MULTI TYPE
2-3 rooms type
12. External input and output
12-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
The wire connection should be separate from the power cable line.
Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
Indoor unit
type
External input External output
Control input
Operation
status output
Fresh air
control output
Auxiliary
heater output
Error status
output
Compact
cassette
●●●
Slim duct
Wall mounted
(ASU7/9/12/
15RLF1)
Floor
Indoor unit type Connector
Compact cassette CN102
Slim duct CN102
Wall mounted
ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU15RLF1 CNA01
ASU18RLF CN14
Floor AGU9RLF, AGU12RLF, AGU15RLF CN14
Unit operation Initial setting after power is on
Starting mode other than initial
setting
Operation mode Auto changeover Mode at previous operation
Set temperature 76 °F (24 °C) Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing: off) Air direction at previous operation