EasyManua.ls Logo

Fujitsu AOU18RLXFZH - Capacity Compensation Rate for Pipe Length and Height Difference; Model: AOU24 RLXFZH

Fujitsu AOU18RLXFZH
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 209 -
OUTDOOR UNIT
AOU24RLXFZH
7. Capacity compensation rate for pipe length and height
difference
7-1. Model: AOU24RLXFZH
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Indoor unit: 7,000 Btu
COOLING
Pipe length
m 5 7.510152025
m ft 162533496682
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 49 - - - 0.956 0.942 0.928
10 33 - - 0.977 0.963 0.950 0.936
7.5 25 - 0.988 0.981 0.967 0.953 0.940
5 16 0.995 0.992 0.985 0.971 0.957 0.943
0 0 1.003 1.000 0.993 0.979 0.965 0.951
Indoor unit is lower than
outdoor unit *2
-5 -16 1.003 1.000 0.993 0.979 0.965 0.951
-7.5 -25 - 1.000 0.993 0.979 0.965 0.951
-10 -33 - - 0.993 0.979 0.965 0.951
-15 -49 - - - 0.979 0.965 0.951
HEATING
Pipe length
m 5 7.510152025
m ft 162533496682
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 49 - - - 0.977 0.958 0.939
10 33 - - 0.993 0.977 0.958 0.939
7.5 25 - 1.000 0.993 0.977 0.958 0.939
5 16 0.990 1.000 0.993 0.977 0.958 0.939
0 0 0.990 1.000 0.993 0.977 0.958 0.939
Indoor unit is lower than
outdoor unit *2
-5 -16 0.985 0.995 0.988 0.972 0.953 0.934
-7.5 -25 - 0.993 0.986 0.970 0.951 0.932
-10 -33 - - 0.983 0.967 0.948 0.930
-15 -49 - - - 0.962 0.944 0.925
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH