- 29 -
MULTI TYPE
2-3 rooms type
Model name ARU18RLF
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 18,000
Input power W73
Running current A0.44
Fan
Airflow rate
Cooling
HIGH
CFM (m
3
/h)
554 (940)
MED 518 (880)
LOW 483 (820)
QUIET 442 (750)
Heating
HIGH 554 (940)
MED 518 (880)
LOW 483 (820)
QUIET 442 (750)
Type × Q'ty Sirocco × 3
Motor output W 81
Recommended static pressure inWG (Pa) 0 to 0.36 (0 to 90)
Sound pressure level *2
Cooling
HIGH
dB (A)
32
MED 31
LOW 30
QUIET 29
Heating
HIGH 33
MED 32
LOW 31
QUIET 29
Heat exchanger type
Dimensions (H × W × D) in (mm)
11-9/16 × 27-9/16 × 1-9/16
(294 × 700 × 39.9)
Fin pitch FPI 20
Rows × Stages 3 × 14
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Galvanized steel sheet
Color -
Dimensions
(H × W × D)
Net
in (mm)
7-13/16 x 35-7/16 x 24-7/16
(198 × 900 × 620)
Gross
10-13/16 x 45-1/16 x 30-3/8
(274 × 1,145 × 772)
Weight
Net
lb (kg)
49 (22)
Gross 60 (27)
Connection pipe
Size
Liquid
mm (in)
Ø1/4 (Ø6.35)
Gas Ø1/2 (Ø12.70)
Method Flare
Drain hose
Material HARD PVC
Size in (mm) Ø 3/4(I.D.), Ø 1-1/16(O.D.) [Ø 20.7 (I.D.), Ø 26.6 (O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Remote controller type Wired (Wireless [option])
NOTES:
Specifications are based on the following conditions.
Standard static pressure: 0.10 inWG (25 Pa)
The protective function might work when using it outside the operation range.
*Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.