02 - 17
)
-
OUTDOOR UNIT
AOU18-36RL
OUTDOOR UNIT
AOU18-36RL
SAFETY DEVICES10.
Protection form
Model
AOU18RLB AOU24RLB AOU30RLXB AOU36RLXB
Circuit protection
Current fuse
(NEAR THE TERMINAL)
5A 250V
Current fuse
(MAIN PRINTED CIRCUIT
BOARD)
3.15A 250V x 2
Fan motor
protection
Thermal protection
program
OFF : 212±
27
°F (100±
15
°C)
ON : 203±
18
°F (9
10
°C)
OFF : 302±
27
°F (150±
15
°C)
ON : 248±
27
°F (12
15
°C)
High Pressure
Protection
Pressure Switch
OFF : 4.2±0.1MPa
ON : 3.0.15MPa
Compressor
protection
Thermal protection
program
(COMPRESSOR TEMP.)
-
OFF : 226°F (108°C)
ON : 176°F (80°C)
Thermal protection
program
(DISCHARGE TEMP.)
OFF : 230 °F (110 °C)
ON : After 7 minutes
Thermal protection
program
(OUTDOOR TEMP.)
(Cooling/Dry mode)
OFF : 5°F (-15°C)
ON : 14°F (-10°C)
OFF : -1F (-25°C)
ON : -4°F (-20°C)