1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• →hen the room temperature is within the range of +6.0 °C to -1.0 °C of the setting temperature,
the rotation number of compressor is controlled within the range shown in the table below. Howev-
er, the maximum rotation number is limited in the range shown in the figure below based on the
indoor fan mode and the outdoor temperature.
• Rotation number range of compressor
Unit: rps
Model name Minimum frequency Maximum frequency
AS↔G07KGTE 12 62
AS↔G09KGTE 12 67
AS↔G12KGTE
AS↔G14KGTE
12 83
1-1. Cooling operation - (04-1) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS