10. Electrical characteristics
Model name AOYG07KMCC AOYG09KMCC AOYG12KMCC AOYG14KMCC
Power
supply
Voltage V 230 ~
Frequency Hz 50
Max operating current *1 A 9.0
Starting current A 3.0 3.4 5.1 6.8
Wiring
spec. *2
Circuit breaker current A 15
Power cable
mm
2
1.5
Connection
cable *3
Cross-
sectional
area
mm
2
1.5
Limited
wiring
length
m 21
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 57 -