Model: AUXG18KVLA
Outdoor temperature
Indoor temperature (°CDB / °CWB)
18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0
(°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
-10.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
-5.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
0.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
5.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
10.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
15.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
20.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
25.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
30.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
35.0 4.80 2.91 5.42 3.31 5.72 3.81 6.12 4.28 6.54 4.69 6.74 5.37
40.0 3.93 1.95 4.45 2.23 4.69 2.56 5.02 2.88 5.36 3.15 5.53 3.61
46.0 3.07 1.19 3.47 1.36 3.66 1.56 3.92 1.75 4.19 1.92 4.32 2.20
NOTES:
• TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW)
• Values mentioned in the table are based on the following conditions:
– Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)
- 374 -
6-2. Cooling capacity 6. Capacity table
OUTDOOR UNIT
AOYG18-24KBTA3
OUTDOOR UNIT
AOYG18-24KBTA3