10. Electrical characteristics
Model name AOHG24LBCB
Power supply
Voltage V 230 ~
Frequency Hz 50
Max operating current *1 A 15.7
Starting current A 9.9
Wiring spec. *2
Circuit breaker current A 20
Power cable
mm
2
2.5
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length m 31
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri-
ate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor
size.
- 49 -
OUTDOOR UNIT
AOHG24LBCB