6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOYG22KBTB
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *
1
25 0.909 0.909 0.903
15 0.953 0.950 0.947 0.941
10 0.983 0.968 0.966 0.962 0.956
7.5 0.988 0.987 0.972 0.970 0.966 0.960
5 0.992 0.992 0.991 0.976 0.974 0.970 0.964
0 1.000 1.000 0.999 0.984 0.982 0.978 0.972
Indoor unit is lower than
outdoor unit *
2
-5 1.000 1.000 0.999 0.984 0.982 0.978 0.972
-7.5 1.000 0.999 0.984 0.982 0.978 0.972
-10 0.999 0.984 0.982 0.978 0.972
-15 0.984 0.982 0.978 0.972
-25 0.982 0.978 0.972
HEATING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *
1
25 0.894 0.867 0.839
15 0.920 0.894 0.867 0.839
10 0.982 0.920 0.894 0.867 0.839
7.5 1.000 0.982 0.920 0.894 0.867 0.839
5 1.000 1.000 0.982 0.920 0.894 0.867 0.839
0 1.000 1.000 0.982 0.920 0.894 0.867 0.839
Indoor unit is lower than
outdoor unit *
2
-5 0.995 0.995 0.977 0.916 0.889 0.862 0.836
-7.5 0.993 0.975 0.913 0.887 0.860 0.832
-10 0.972 0.911 0.885 0.858 0.830
-15 0.902 0.876 0.849 0.821
-25 0.851 0.821 0.795
- 39 -
6-1. Model: AOYG22KBTB
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG22KBTB
OUTDOOR UNIT
AOYG22KBTB